Valve selection
Q915F-16T electric three-way internal thread brass ball valve
Product positioning
The electric three-way internally threaded brass ball valve Q915F-16T is designed for HVAC, building automation, equipment matching, and small-diameter process pipelines. It adopts the T type three-way internally threaded ball reversing structure and is used for three-way diversion, merging, and flow direction switching of cold and hot water, air, and general non corrosive media. The combination of valves and electric switch type actuators can be connected to the on-site control system, allowing manual operation points to be converted into monitored and interlocked automatic control nodes. Fouten Flow Control (Jiangsu) Co., Ltd. determines materials and actuators based on the medium, pressure difference, operating frequency, and safe position, and does not use similar shapes to replace specific operating conditions for selection.
Action and sealing characteristics
The output of the actuator is transmitted to the opening and closing components through the connecting components, causing the three-way ball to rotate and change direction at a specified angle. PTFE soft seal forms the main sealing interface, and the brass valve body bears the pipeline pressure and connection load. The actual closing ability is simultaneously affected by pressure difference, temperature, medium particles, sealing pre tightening, and opening and closing speed. After the control system issues a command, it should confirm the end of the action through in place feedback; If the feedback exceeds the time limit, continuous forced driving is not allowed to avoid damaging the valve stem, seal or actuator.
Selection Information
Before placing an order, it is necessary to confirm the actual diameter within the range of DN15-DN50, the design pressure of PN16, the working temperature from - 10℃ to 120℃, as well as the composition, concentration, viscosity, and solid content of the medium. Simultaneously explain the normal and maximum flow rates, pressure before and after the valve, number of actions, power or gas source conditions, requirements for faulty switches, and on-site protection level. The material combination of the electric three-way brass ball valve must be compatible with hot and cold water, air, and general non corrosive media; High frequency operation, long-term shutdown, crystallization medium or outdoor corrosive environment should increase corresponding safety factors and protective measures.
Product Specifications
| Product Model | Q915F-16T |
| Structural form | T Type Three way Internal Thread Ball Reversing Structure |
| Nominal Diameter | DN15-DN50 |
| pressure rating | PN16 |
| Valve body material | Brass |
| sealing form | PTFE Soft Seal |
| Drive Type | Electric switch type actuator |
| Applicable temperature | -10℃ to 120℃ |
| Applicable Medium | Cold and hot water, air, and general non corrosive media |
| Application Industry | HVAC, building automation, equipment matching, and small-diameter process pipelines |
| Product Features | Three way diversion, merging, and flow direction switching |
Installation inspection
After arrival, first check the nameplate, model, interface, material, and accessories, and inspect for any bumps, looseness, or moisture during transportation. Before installation, remove welding slag, sand particles, and sealing debris from the pipeline, ensure that the interfaces at both ends are coaxial, and provide independent support for the pipeline and actuator. Do not use bolts to forcibly pull the interface in a positive or negative position, and do not let cables, air pipes, or accessories bear the weight of the valve. Position according to the valve body identification and process flow direction, while reserving space for disassembly, manual operation, and replacement of seals.
Debugging steps
The first debugging starts from no pressure point movement, checking the opening direction, mechanical limit, valve position indication, and feedback contacts, and then conducting a full stroke test. Check the voltage, phase sequence, grounding, overload protection, and cable sealing of electric products; Check the cleanliness of the air source, filtration and pressure reduction, direction of the solenoid valve, and air circuit leakage for pneumatic products. Subsequently, observe the action time and seal closure under low-pressure medium conditions, confirm that the local, remote, and emergency interlocks are consistent, and finally gradually increase to the working pressure and record the benchmark data.
operation and maintenance
Regularly check for external leaks, abnormal sounds, actuator temperature rise, loose connections, and changes in action time during operation. When it is found that the closure is not tight, first check the limit, pressure difference, debris, and seal wear; Check the power or gas source, transmission resistance, and valve stem coaxiality when the movement is slow. The replacement parts for maintenance must be consistent with the grade and size of the raw materials, and after completion, recalibrate the limit, feedback, and fault location. For media containing particles or prone to sedimentation, a flushing and periodic action plan should be developed to avoid a significant increase in starting torque after shutdown.
Safety maintenance
Before maintenance, close the upstream and downstream isolation points, drain the pressure and residual liquid, and lock the power or gas source. Only after confirming that there is no pressure in the valve chamber and the surface temperature is safe can it be disassembled; Toxic, corrosive, or flammable media must also undergo displacement testing and personal protection requirements. The common selection question is whether the actuator can be selected only based on the diameter, and the answer is no. It also needs to be calculated based on the maximum pressure difference, sealing friction, and fault safety factor. Before putting into operation, sealing, action, feedback, and interlocking re inspection should be completed, and isolation can only be lifted after the records are qualified.
Common problems in selection and procurement
Can Q915F-16T switch one water channel to two branches?
You can choose the desired reversing function, but you need to first draw three interface numbers and the channels that need to be connected at each position. T type opening does not mean that all switching positions can block the common entrance; When it is necessary to completely shut off or avoid the flow of hot and cold water, the ball opening and actuator limit should be checked separately.
There are already threaded fittings on site, can we directly screw on this ball valve?
First confirm the interface size, thread standard, internal and external threads, and sealing method, and then verify the pressure and installation space. The same DN cannot prove that threads of different standards can be interchanged, and tightening force cannot be applied through the actuator housing during installation.
Can it automatically switch to the bypass port when there is a power outage?
Ordinary electric configurations cannot default to having power-off reversing function. When it is necessary to cut off power and bypass, please specify the target interface combination, allowable switching time, and power supply conditions, and then confirm the energy storage or backup power supply plan and feedback interlock.