ZDLP electric single seat regulating valve
ZDLP electric single seat regulating valve
ZDLP consists of a single seat regulating valve body, valve core and seat, valve stem, and electric actuator. Denso receives configured control commands, drives the valve core to make linear motion, and adjusts the flow rate by changing the throttling area. It can also serve pressure, temperature, or liquid level control in a complete control loop, but not all variables can be controlled by one valve at the same time.
Single seat structure and closing capacity
The single seat structure has a set of main valve core and seat sealing pairs, and the closing ability depends on the valve internals, sealing form, medium pressure difference, and actuator thrust. We cannot promise the highest accuracy or zero leakage based solely on the name of a single seat. For media containing particles, erosion, blockage, and valve seat damage should be considered, and for larger pressure differentials, unbalanced forces and noise should also be evaluated.
Flow coefficient and operating condition data
The selection should provide the minimum, normal, and maximum flow rates, as well as the upstream and downstream pressure, medium state, density or gas composition, and working temperature for each operating condition. Calculate Cv/Kv and opening range based on these data, and then select valve seat diameter, flow characteristics, and DN. The caliber, pressure, and material listed in the column belong to a series of information and do not represent that any combination is applicable; Large caliber or special pressure configurations require independent confirmation of the manufacturing plan.
Electric actuators and signals
The electric actuator should be matched with the straight stroke, required thrust, stroke, adjustment frequency, and on-site power supply. 4–20mA、 Other analog quantities, switch contacts, or communication interfaces need to be confirmed according to the specific electric actuator and cannot be assumed to be fully supported. The feedback signal should also be specified separately from the input command. The ability to maintain position, open or close valves after power failure depends on the actuator and energy storage circuit, and is not automatically guaranteed by the ZDLP model.
Materials, Installation, and Maintenance
The materials for the valve body and internal components should be selected according to corrosiveness, temperature, and erosion conditions, and the packing and gasket should also be compatible. Install according to the valve body flow direction markings, leaving sufficient space for actuator and valve internals maintenance, and setting up necessary isolation and bypass. Check the full travel, feedback, limit and loop direction during operation; Isolate, depressurize, drain and lock the power supply before dismantling and inspection.
Common problems in selection and procurement
I only have pipe diameter and flow rate, can I directly choose ZDLP?
The minimum, normal, and maximum flow rates corresponding to the pressure, medium, and temperature before and after the valve can be calculated for Cv/Kv, allowable pressure difference, and operating opening. Only selecting valves based on pipe diameter may result in long-term low opening operation, unstable adjustment, or insufficient thrust.
Can ZDLP connect to the existing 4–20mA of DCS?
Configuration requirements can be proposed based on this signal, but the input, feedback, power supply, and signal isolation methods of the actual actuator must be verified. It cannot be assumed that any electrical device is compatible. Please provide the wiring requirements for DCS together with the inquiry.
After a power outage, the process requires the valve to be closed. How can I place an order?
Please specify the maximum closing pressure difference, required closing time, and fail safe location before confirming the actuator plan with energy storage or backup energy. Ordinary electric control valves cannot automatically close when power is lost by default.